Q1: Kungani ukuphindaphinda kabili (150Hz kuya ku-200Hz) kuyisibopho sokuhlolwa{3}}kwe-voltage PD ku-40 MVA transformer?
IMP: Lapho sihlola ukufakwa kwe-longitudinal kwe-transformer (ungqimba-lokujika nokuphakathi{1}}), sisebenzisa i-voltage ephakeme kakhulu kunenani elilinganiselwe (imvamisa engu-1.5x). Uma sisebenzisa umthombo ojwayelekile we-50Hz/60Hz, umgogodla wensimbi ubungangena ngokushesha ekugcwaleni kazibuthe, okubangele ukuthi i-excitation yamanje inyuke futhi ibulale ama-windings. Ngokusho kwefomula kazibuthe ye-flux (Φ=U/4.44fNΦ=U/4.44fN), ngokwandisa imvamisa ukuya ku-150Hz noma ku-200Hz, singakwazi ukuzuza amandla kagesi okuhlola aphezulu kuyilapho sigcina i-core flux isezingeni eliphephile, elingagcwalisi{13}.
Q2: Singalifinyelela kanjani izinga lomsindo elingemuva elingu-< 10pC ngesikhathi sokuhlolwa kwe-transformer ye-onsite 66kV?
IMP: Ukuthola umsindo ophansi kangako endaweni yenkundla kudinga indlela ehlelekile:
Ukuhlunga Kwezingxenyekazi Zekhompyutha: Ukusebenzisa Umthombo Wamandla Oshintshashintshayo onesihlungi esihlanganisiwe esisindayo-semisebenzi ye-LC ukuvimba-umsindo wefrequency ephezulu osuka ekushintsheni kwe-IGBT.
Ukuthuthukisa Inkambu Kagesi: Ukufaka-i-diameter Grading Shield (Corona Ring) enkulu kuma-66kV bushings ukuze kuqedwe i-air corona.
Umqondo Wokusungula: Ukusebenzisa-isistimu yephoyinti elilodwa lenkanyezi ukuvimbela amaluphu aphansi asebenza njengezimpondo ze-EMI.
Ikhebula: Ukusebenzisa{0}}izintambo zokulinganisa ezivikelwe kabili ukuze kuvikelwe amasiginali e-PD azwelayo ekuphazamisekeni kwe-ambient.
Q3: Yiziphi izindlela zokudlula/zokwehluleka ukuhlolwa kwe-PD yesiguquli esingu-66kV ngokuya nge-IEC 60076-3?
A: Kuma-transformer ane-Um=72.5 kVUm{1}} kV (66kV class), izinga ngokuvamile lidinga ukuthi phakathi{3}}nokuqapha kwamandla kagesi enziwe isikhathi eside (ngokuvamile ku-1.5Um/31.5Um /3), izinga Lokukhipha Ingxenye kufanele lihlale lingaphansi kuka-100pC. Okubaluleke kakhulu, ukuthambekela kwePD kumele kuzinzile; noma yikuphi ukunyuka okuqhubekayo kobukhulu bokukhipha noma izinga lokushaya kwenhliziyo phakathi nobude besikhathi sokuhlolwa kwamaminithi angu-30–60 kuthathwa njengokuhluleka, ngisho noma inani eliphelele lingaphansi kuka-100pC.
Q4: Ngingakwazi ukusebenzisa i-AC Hipot Test Transformer evamile esikhundleni se-Varable Frequency System?
A:I-transformer yokuhlola yendabuko ingenza i-Ukuhlola Okuhlukile Komthombo Wokumelana(i-insulation enkulu emhlabathini). Nokho, kunjaloayifanelekikokubaluleke kakhuluUkuhlolwa Kwe-Voltage Okufakiwekuyunithi engu-40MVA ngoba ayikwazi ukunikeza imvamisa eyengeziwe edingekayo (150Hz+) ukuze igweme ukugcwaliswa kwesikhala okubalulekile. Ngaphezu kwalokho, iziguquli zokuhlola zendabuko zisinda kakhulu futhi kunzima ukuzithutha ziye eziteshini ezikude ezingama-66kV uma kuqhathaniswa nezinhlelo zemodular Variable Frequency.
Q5: Iyini inzuzo yokusebenzisa umtapo wolwazi wezigxivizo zeminwe we-2D/3D PRPD kusofthiwe yokuxilonga?
A: Umtapo wezincwadi wesigaba-Okuxazululiwe Ukukhipha Okuyingxenye (PRPD) uvumela onjiniyela ukuthi badlulele ngale kwemiphumela elula ethi "Pass/Fail". Ngokuqhathanisa amaphethini okukhishwa (umumo, ukuma kwesigaba, kanye nemvamisa) kusizindalwazi seziphambeko ezaziwayo, isistimu ingakwazi ukuhlonza ngokuzenzakalela uhlobo lwamaphutha-njengokubonakala okucijile ku-conductor, izinhlayiya zensimbi ezintantayo kuwoyela, noma igebe ku-insulation eqinile. Lokhu "Isistimu Yochwepheshe" inciphisa kakhulu ingozi yephutha lomuntu ngesikhathi sokuhlaziywa kwedatha ye-onsite.