Ukuvikela Inhliziyo Yegridi: Ukuhlaziywa Kobuchwepheshe Kokukhishwa Okuyingxenye (PD) Ukuhlola Ama-66kV 40MVA Transformers

 Aug 21, 2026

 Shiya umlayezo

 

Ekusebenzeni kwamagridi{0}}amandla kagesi aphezulu wesimanje, ukuthembeka kokufakwa kwama-transformer kuyitshe legumbi lokuzinza kwesistimu. Njengoba kuqashelwa njenge-"ECG" ezwela kakhulu yokuhlola impilo ye-dielectric, ukuhlolwa kwe-Partial Discharge (PD) sekuyisidingo esiyisibopho sokugunyazwa nokugcinwa kweziguquli zikagesi ezilinganiselwe ku-66kV nangaphezulu.

Muva nje, mayelana nezidingo zokuhlola endaweni yamayunithi-anamandla aphezulu (40MVA), imboni izibandakanye ezingxoxweni ezijulile zokulinganisa amandla okuhlola nokunciphisa umsindo ongemuva. Lesi sihloko siveza umqondo wobunjiniyela oyinhloko ngemuva kokuzuza indawo "PD Free" yesiguquli esingu-66kV 40MVA.

I. Kungani Kufanele I-40MVA Transformers Ihlole Ukuhlolwa Kwe-PD?

Ngokungafani nokuhlolwa okujwayelekile komthombo ohlukile we-AC Withstand (Hipot), ku-transformer enkulu engu-40MVA, amaphutha anamandla avame ukufihlwa ekujuleni kwama-windings, afana{1}}nokufakwa phakathi kokushintshashintsha noma ukuthepha{2}}izixhumi ezibonakalayo zokushintsha.

Ngokwezinga le-IEC 60076-3:2013, ama-transformer anevoltheji yesistimu enkulu ye-Um=72.5 kV; Um​=72.5 i-kV kufanele ihlolwe i-Induced Voltage nge-PD Measurement (IVPD). Izinzuzo eziyinhloko zihlanganisa:

Ukufakwa Okubanzi: Ngokujabulisa okuvela ohlangothini lwe-LV kanye nokufaka amandla kagesi angu-1.5x ohlangothini lwe-HV, kokubili ukwahlukanisa okuyinhloko kanye nokufakwa kwe-longitudinal (-ku-inter{1}}kujika) kugcizelelwa ngokwangempela.

Uhlelo Lwesexwayiso Sangaphambi kwesikhathi: Ukuhlolwa kwe-PD kungathwebula ukukhishwa okuncane okubangelwa amabhamuza egesi kuwoyela, ama-burrs asongayo, noma ukuguga kokuvikela, ukuvimbela ukwehluleka okuyinhlekelele ngaphambi kokuba kwenzeke.

 

II. I-Frequency Doubling Technology: Isihluthulelo Sokunqoba Ukugcwala Kwezibuthe

Lapho senza ukuhlolwa kwe-voltage engenisiwe kusiguquli esingu-40MVA, imithombo yamandla evamile engu-50Hz/60Hz ibhekana nesithiyo esibalulekile: Ukugcwaliswa Kwezimboni Eziyisisekelo.

Ngokuya ngemithetho yokungeniswa kwe-electromagnetic, uma i-voltage elinganiselwe engu-1.5x isetshenziswa ku-50Hz, i-core flux ikhula kakhulu, okuholela ekuqubukeni kwamandla okuvusa amandla okungashisa ama-winding. Ukuxazulula lokhu, onjiniyela basebenzisa i-Frequency Doubling (isb, 150Hz - 200Hz). Le ndlela igwema ukugcwaliswa kukazibuthe kuyilapho yehlisa ngokuphawulekayo usayizi wezinto zokuhlola, okwenza kube -ukuhlolwa kwesayithi ukuthi kube nokwenzeka.

 

III. Izinsika Ezine Zokuthola Imvelo

Ukwehlisa umsindo ongemuva wesistimu ye-66kV ngaphansi kuka-10pC endaweni yasensimini kuyinselele enkulu. Izixazululo zobuchwepheshe ezihamba phambili ngokuvamile zihlanganisa lezi zinyathelo ezilandelayo:

1. Okuphezulu{1}}Ukusebenza Okugcwele-I-Loop Filtering

Ukusebenzisa i-PD-Imithombo Yamandla Eguquguqukayo Yamahhala Yamahhala efakwe izihlungi ezisindayo-zemisebenzi ye-LC. Lokhu kunqamula ukuphazamiseka okwenziwe kusukela{3}}ekushintsheni kwemvamisa ephezulu kwama-IGBT e-inverter, okuqinisekisa ukuphuma kwe-waveform okumsulwa.

2. Ukuthuthukiswa Kwenkundla kanye Nokucindezela I-Corona

Izivikelo Zokugreda{0}ezipholishiwe eziqondile{0}(Izindandatho Ze-Corona) ezinobubanzi okungenani obungu-800mm phezulu kwamabhushi angu-66kV. Le mininingwane icindezela amasiginali angamanga akhiqizwa i-air corona, iqinisekisa ukuthi konke ukufundwa kwe-PD kukhombisa isimo sangempela sangaphakathi se-transformer.

3. Ama-Capacitor Okuhlanganisa{1}Anembile

I-Specialized PD-ama-coupling capacitor amahhala asebenza njengesixhumi esibonakalayo esikhipha isignali. Ukulahlekelwa kwabo okuphezulu kakhulu-okuphansi kwe-dielectric kubalulekile ekutholeni Isiginali ephezulu-kuya-ku-Noise Ratio (SNR) yama-pulses okukhipha.

4. Amasistimu Wokuxilonga Ochwepheshe

Izitholi zesimanje ze-PD yedijithali (ezifana ne-PD-nochungechunge luka-2000) zihlanganisa i-2D/3D PRPD (Ukukhishwa Okuyingxenye Okuxazululiwe Kwesigaba) amalabhulali wezigxivizo zeminwe. Ngokusebenzisa ama-algorithms ahlakaniphile, isistimu ingakwazi ukuhlukanisa ngokuzenzakalelayo phakathi komsindo wangaphandle, ukuphuma kwephoyinti, noma ukukhubazeka kwangaphakathi kwama-electrode antantayo.

 

Ngesiguquli esingu-66kV 40MVA, icebo lokuhlola le-PD eliphelele alidingi nje kuphela ihadiwe eqinile kodwa futhi nokuqonda okujulile kwendawo kagesi kazibuthe. Ukukhetha uhlelo oludidiyelwe lwe-"Variable Frequency Resonance + Induced Frequency Doubling" njengamanje kuyindlela eyaziwa emhlabeni wonke yezinkampani zensiza ukuze zithole ukuphathwa kwempahla okuphumelelayo nokunembayo.

Thumela ukuPhenya
Thumela ukuPhenya